Technical Characteristics
|
Number of modules: |
16 |
|
Number of poles: |
4 P |
|
Rated operational voltage Ue: |
220/690 V |
|
Rated current: |
1600 A |
|
Rated service breaking capacity Ics AC according IEC 60947-2: |
100 % |
|
Range of the magnetic adjustment: |
8960/11200/14000/17920/19200/19200/19200 A |
|
Total power loss under IN: |
168,9 W |
|
Frequency: |
50/60 Hz |
|
Rated insulation voltage: |
800 V |
|
Rated impulse withstand voltage: |
8000 V |
|
Operating temperature: |
-25 to 70 °C |
|
Electric endurance in number of cycles: |
1000 |
|
Number of mechanical operations: |
4000 |
|
Connection cross-sect. rigid cable: |
3x240mm² |
|
Connection cross-sect. flexible conductor: |
3x240mm² |
|
Tightening torque: |
65Nm |